Pv Combiner Box Solar Combiner Box Pv Solar Combiner Box
• Design and configuration strictly accordance with the "Technical specification for photovoltaic junction equipment" CGC/GF 037:2014.
• Provide users with a safe, brief, beautiful and applicable photovoltaic system products.
The product adopts outdoor wall mounted type, which adapt to the harsh environment. In addition to the core components, the other can be customized by users requirements.
• For a large PV power generation system,In order to reduce the grid connection between the grid -connected inverter and the cabinet,It is convenient to maintain and improve the reliability.It is necessary to add a DC bus between the PV grid-connected inverter and the cabinet. PV AC lightning protection combiner box series products of the company is specially designed to meet this requirement ,Can be composed of PV inverter products matching with complete PV system solutions.Using AC combiner box ,the user can according to the AC power cabinet rated input current and voltage ,the output of a certain number of grid connected inverter by lightning protection device and circuit breaker for confluence,convenient access level power cabinet.

Normal service conditions of switchgear as follows: | |
Ambient temperature: | |
Maximum |
+40°C |
Maximum 24 hour average |
+35°C |
Minimum |
-25°C |
Ambient humidity: | |
Daily average relative humidity |
less than 95% no condensation |
Monthly average relative humidity |
less than 90% no condensation |
Earthquake intensity |
less than 8 degree |
Height above sea level |
less than 2000m |
This product should not be used under conditions of fire, explosion, earthquake and chemical corrosion environments.
Product Parameters
Name |
SHLX-PV |
System maximum dc voltage |
1000 |
Maximum input current for each string |
6A-30A |
Maximum input strings |
24 |
Maximum output switch current |
400A |
Number of inverter MPPT |
N |
Number of Output strings |
1 |
Category of test |
‖ grade protection |
Nominal discharge current |
20ka |
Maximum discharge current |
40ka |
Voltage protection level |
3.8kv |
Maximum continuous operating voltage Uc |
1050A |
Poles |
3P |
Structure characteristic |
Plug-push module |
Protection grade |
IP65 |
Output switch |
DC isolation switch(standard)/DC circuit |
DC MC4/DC FUSE/DC Surge Protector |
Standard |
Monitoring module/Preventing diode |
Optional |
Installation method |
Wall mounting type |
Model | SHLX-FL24 | SHLX-FL16 | SHLX-FL12 | SHLX-FL8 |
Input channel number | 17~24 | 13~16 | 8~12 | Less than 8 |
Max. input voltage | 1000Vdc | |||
Input current of each channel | 0~20A | |||
Max. output current | 250A | 160A/200A | 100A/125A/160A | 100A Less than 100A |
Size of the input waterproof terminal | PG9/PG11 | |||
Size of the output waterproof terminal | PG21~PG29 | PG19~PG25 | PG16~PG21 | PG13.5~PG19 |
Monitoring module(optional) | Detect current of each channel, bus voltage, status of circuit breaker and lightning protector, box temperature | |||
Communication mode/protocol(optional) | RS485 bus/standard MODBUS-RTU protocol | |||
Prevent-reverse function | Can be equipped with modularized and encapsulated prevent-reverse diode (optional) | |||
Temperature and humidity | Operating temperature: -40~+85ºC, humidity 95%, places free of dew or corrosive gas. | |||
Altitude | ≤4000m | |||
Power consumption of monitoring module | Working hours≤8W | |||
Auxiliary power supply | Auxiliary power supply: AC85V~265V/DC24V(±10%)/DC200V~1000V | |||
Box material | Hot galvanized steel/stainless steel/cold rolled sheet/engineering plastics | |||
Ingress protection | IP65 | |||
Volume (W×H×D) | 850*500*200 | 800*500*180 | 720*500*180 | 650*500*180 |
Weight | 10~35kg |
Model | SHLX-FL24 | SHLX-FL16 | SHLX-FL12 | SHLX-FL8 |
Input channel number | 17~24 | 13~16 | 8~12 | Less than 8 |
Max. input voltage | 1000Vdc | |||
Input current of each channel | 0~20A |
Feature
- Ingress protection of the combiner box reaches IP65, it is featured with waterproof, dust-proof,
rustproof, salt fog proof, can be used outdoors.
- Put in 24 channels of PV strings at most.
- Positive and negative poles of each PV string are equipped with special fuse wire,
which protects the PV string from fault, use match-able fuse holder and fuse wire to reduce later
maintenance cost for owner, and guarantee safety of maintenance personnel.
- It uses photovoltaic purposed HV lightning protector to carry out protection to the positive
pole-to-ground and negative pole-to-ground of bus after combination,
the continuous operating voltage reaches 1000VDC.
- The power supply module in the combiner box can accept PV voltage as high as 1000DCV.
- The measure-control module of combiner box adopts high-performance Honeywell Hall elements (DC CT sensor), which carries out monitoring, alarm
and local fault location to each PV string, meanwhile, it measures the temperature inside the combiner
box, carries out status inspection to the lightning protector and output circuit breaker.
- Monitoring module in the combiner box has function of digital display, it indicates the current
of each PV string, bus voltage, temperature inside the box, status of circuit breaker and lightning
protector, system power, equipment address and other relevant information.
- It is equipped with RS485/MODBUS-RTU serial port communication.
- All external interfaces have lightning protection.
- Receive and download the parameters of local monitoring device, and carry
out analysis processing.
- Working power supply for combiner box can be 220VAC/DC from outside,
also can be supplied by the self-contained power supply of combiner box. When using the self-contained power supply, users need not to arrange additional wiring for the power supply.