SZC(B)-10 SZC(B)-11 SZC(B)12 SZC(B)13 series intelligent 3 -Phase indoor dry-type Distribution transformer

Short Description:

  • This product conforms to the national standard GB1094.1-2013(IEC 60076) power transformer and GB / T6451-2015 indoor dry-type transformer technical parameters and requirements.
  • Epoxy resin pouring transformer is a solid insulation encapsulated winding power transformer.
  • Epoxy resin dry-type transformer uses epoxy resin as insulation material.High and low voltage winding is made of copper strip (foil), epoxy resin is poured and solidified in vacuum to form high strength FRP body. Insulation grade is F and H.
  • Epoxy resin dry-type transformer has the characteristics of good electrical performance, strong lightning shock resistance, strong short-circuit resistance, small size and light weight etc.. The temperature display controller can   be installed to display and control the operating temperature of the transformer winding to ensure the normal service life of the transformer.

Product Detail

Product Tags

Compared with the manual voltage regulation of traditional SCB series indoor dry 3-phase power transformer, SZC(B)-10  SZC(B)-11  SZC(B)12 SZC(B)13 series  intelligent 3- Phase indoor dry-type Distribution transformer can realize the load through the controller on the ground remote power transformer to adjust the voltage, which can realize free power voltage regulator, reducing frequency of climbing and risk, greatly convenient for power operation personnel on site.

MODEL: SCZB-13 □ □

SC: Three-phase Solid molding (epoxy pouring)
Z: Voltage can be adjust Auto
B: Low prssure "foil"coil
13: Performance level code
□: The rated capacity (kVA)
□: High pressure rated voltage (kV)
f

RATED

1. Capacity: 10kVA up to 31500kVA

2. High Voltage: 3.3kV up to 35kV

3. Connection Method: Optional

4.Rated Low Voltage: 0.4kV 3.15kV 6.3kV 6.6kV10.5kV

5.Rated frequency:50Hz

6.HV tap range: ±2.5%, ±5%

7.Material: Full copper Winding

 

Service conditions of indoor dry-type transformer

Device types:

outdoor type

Ambient temperature:

Maximum

+40°C

Maximum 24 hour average

+35°C

Minimum

-25°C (-45°C when you order details0

Ambient humidity:

Height above sea level at site

less than 1000m

Earthquake intensity

less than 8 degree

Height above sea level

less than 1000m

Mounting ambicnt:

No fire, explosion, earthquake and chemical corrosion environments.

Technical parameters of indoor dry-type transformer(10kV grade)

Technical parameters of SC(B)10 series 6kV, 10kV grade non-excitation voltage regulating distribution dry type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

30

6
6.3
6.6
10
10.5
11

±2.5
±5

0.4

Dyn11
Yyn0

0.19

0.67

0.71

0.76

2

5.5

50

0.27

0.94

1

1.07

2

80

0.37

1.29

1.38

1.48

1.5

100

0.4

1.48

1.57

1.69

1.5

125

0.47

1.74

1.85

1.98

1.3

160

0.54

2

2.13

2.28

1.3

200

0.62

2.37

2.53

2.71

1.1

250

±2×2.5
±5

0.72

2.59

2.76

2.69

1.1

315

0.88

3.27

3.47

3.73

1

400

0.98

3.75

3.99

4.28

1

500

1.16

4.59

4.88

5.23

1

630

1.34

5.53

5.88

6.29

0.85

630

1.3

5.61

5.96

6.4

0.85

6

800

1.52

6.55

6.96

7.46

0.85

1000

1.77

7.65

8.13

8.76

0.85

1250

2.09

9.1

9.69

10.3

0.85

1600

2.45

11

11.7

12.5

0.7

2000

3.05

13.6

14.4

15.5

0.7

2500

3.6

16.4

17.1

18.4

0.85

1600

2.45

12.2

12.9

13.9

0.7

8

2000

3.05

15

15.9

17.1

0.7

2500

3.6

17.7

18.8

20.2

1.07

Technical parameters of SC(B)11 series 6kV, 10kV grade non-excitation voltage regulating distribution dry type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

30

6
6.3
6.6
10
10.5
11

±2.5
±5

0.4

Dyn11
Yyn0

0.17

0.67

0.71

0.76

1.79

4

50

0.24

0.94

1

1.07

1.78

80

0.33

1.29

1.38

1.48

1.34

100

0.36

1.48

1.57

1.69

1.35

125

0.42

1.74

1.85

1.98

1.16

160

0.48

2

2.13

2.28

1.16

200

0.55

2.37

2.53

2.71

0.98

250

±2×2.5
±5

0.64

2.59

2.76

2.69

0.98

315

0.79

3.27

3.47

3.73

0.90

400

0.88

3.75

3.99

4.28

0.90

500

1.04

4.59

4.88

5.23

0.90

630

1.2

5.53

5.88

6.29

0.76

630

1.17

5.61

5.96

6.4

0.77

6

800

1.36

6.55

6.96

7.46

0.76

1000

1.59

7.65

8.13

8.76

0.76

1250

1.88

9.1

9.69

10.3

0.76

1600

2.2

11

11.7

12.5

0.76

2000

2.74

13.6

14.4

15.5

0.63

2500

3.24

16.4

17.1

18.4

0.63

1600

2.2

12.2

12.9

13.9

0.76

8

2000

2.74

15

15.9

17.1

0.63

2500

3.24

17.7

18.8

20.2

0.63

Technical parameters of SC(B)12 series 6kV, 10kV grade non-excitation voltage regulating distribution dry type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

30

6
6.3
6.6
10
10.5
11

±2.5
±5

0.4

Dyn11
Yyn0

0.15

0.67

0.71

0.76

1.58

4

50

0.215

0.94

1

1.07

1.59

80

0.295

1.29

1.38

1.48

1.20

100

0.32

1.48

1.57

1.69

1.20

125

0.375

1.74

1.85

1.98

1.04

160

0.43

2

2.13

2.28

1.04

200

0.495

2.37

2.53

2.71

0.88

250

±2×2.5
±5

0.575

2.59

2.76

2.69

0.88

315

0.705

3.27

3.47

3.73

0.80

400

0.785

3.75

3.99

4.28

0.80

500

0.93

4.59

4.88

5.23

0.80

630

1.07

5.53

5.88

6.29

0.68

630

1.04

5.61

5.96

6.4

0.68

6

800

1.21

6.55

6.96

7.46

0.68

1000

1.41

7.65

8.13

8.76

0.68

1250

1.67

9.1

9.69

10.3

0.68

1600

1.96

11

11.7

12.5

0.68

2000

2.44

13.6

14.4

15.5

0.56

2500

2.88

16.4

17.1

18.4

0.56

1600

1.96

12.2

12.9

13.9

0.68

8

2000

2.44

15

15.9

17.1

0.56

2500

2.88

17.7

18.8

20.2

0.56

Technical parameters of SC(B)13 series 6kV, 10kV grade non-excitation voltage regulating distribution dry type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

30

6
6.3
6.6
10
10.5
11

±2.5
±5

0.4

Dyn11
Yyn0

0.135

0.605

0.64

0.685

1.42

4

50

0.195

0.845

0.9

0.965

1.44

80

0.265

1.16

1.24

1.33

1.07

100

0.29

1.33

1.41

1.52

1.09

125

0.34

1.56

1.66

1.78

0.94

160

0.385

1.8

1.91

2.05

0.93

200

0.445

2.13

2.27

2.44

0.79

250

±2×2.5
±5

0.515

2.33

2.48

2.66

0.79

315

0.635

2.94

3.12

3.35

0.72

400

0.705

3.37

3.59

3.85

0.72

500

0.835

4.13

4.39

4.7

0.72

630

0.965

4.97

5.29

5.66

0.61

630

0.935

5.05

5.36

5.76

0.61

6

800

1.09

5.89

6.26

6.71

0.61

1000

1.27

6.88

7.31

7.88

0.61

1250

1.5

8.19

8.72

9.33

0.61

1600

1.76

9.94

10.5

11.3

0.61

2000

2.19

12.2

13

14

0.50

2500

2.59

14.5

15.4

16.6

0.50

1600

1.76

11

11.6

12.5

0.61

8

2000

2.19

13.5

14.3

15.4

0.50

2500

2.59

15.9

17

18.2

0.50

Technical parameters of indoor dry-type transformer(20kV grade)

Technical parameters of SC(B)10 series 20kV non-excitation distribution dry-type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

50

20
22
24

±2.5
±5

0.4

Dyn11
Yyn0

0.34

1.16

1.23

1.31

2.00

6

100

0.54

1.87

1.99

2.13

1.80

160

0.67

2.33

2.47

2.64

1.50

200

0.73

2.77

2.94

3.14

1.50

250

±2×2.5
±5

0.84

3.22

3.42

3.66

1.30

315

0.97

3.85

4.08

4.36

1.30

400

1.15

4.65

4.84

5.18

1.10

500

1.35

5.46

5.79

6.19

1.10

630

1.53

6.45

6.84

7.32

1.00

800

1.75

7.79

8.26

8.84

1.00

1000

2.07

9.22

9.78

10.4

0.85

1250

2.38

10.8

11.5

12.3

0.85

1600

2.79

13

13.8

14.8

0.85

2000

3.24

15.4

16.3

17.5

0.70

2500

3.87

18.2

19.3

20.7

0.70

2000

3.24

16.8

17.8

19.1

0.70

8

2500

3.87

20

21.2

22.7

0.70

Technical parameters of SC(B)11 series 20kV dry-type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

50

20
22
24

±2.5
±5

0.4

Dyn11
Yyn0

0.31

1.16

1.23

1.31

1.82

6

100

0.48

1.87

1.99

2.13

1.60

160

0.6

2.33

2.47

2.64

1.34

200

0.65

2.77

2.94

3.14

1.34

250

±2×2.5
±5

0.75

3.22

3.42

3.66

1.16

315

0.87

3.85

4.08

4.36

1.17

400

1.03

4.65

4.84

5.18

0.99

500

1.21

5.46

5.79

6.19

0.99

630

1.38

6.45

6.84

7.32

0.90

800

1.57

7.79

8.26

8.84

0.90

1000

1.86

9.22

9.78

10.4

0.76

1250

2.14

10.8

11.5

12.3

0.76

1600

2.51

13

13.8

14.8

0.76

2000

2.92

15.4

16.3

17.5

0.63

2500

3.48

18.2

19.3

20.7

0.63

2000

2.92

16.8

17.8

19.1

0.63

8

2500

3.48

20

21.2

22.7

0.63

Technical parameters of SC(B)12 series 20kV dry-type transformer

Rated capacity kVA

Voltage tap range

Connection symbol

No-load loss kW

Load loss kW

No-load current %

Short circuit impedance %

HV  kV

HV tap range %

LV  kV

130ºC(B)(100ºC)

155ºC(F)(120ºC)

180ºC(H)(145ºC)

50

20
22
24

±2.5
±5

0.4

Dyn11
Yyn0

0.27

1.16

1.23

1.31

1.59

6

100

0.43

1.87

1.99

2.13

1.43

160

0.53

2.33

2.47

2.64

1.19

200

0.58

2.77

2.94

3.14

1.19

250

±2×2.5
±5

0.67

3.22

3.42

3.66

1.04

315

0.77

3.85

4.08

4.36

1.03

400

0.92

4.65

4.84

5.18

0.88

500

1.08

5.46

5.79

6.19

0.88

630

1.22

6.45

6.84

7.32

0.80

800

1.4

7.79

8.26

8.84

0.80

1000

1.65

9.22

9.78

10.4

0.68

1250

1.9

10.8

11.5

12.3

0.68

1600

2.23

13

13.8

14.8

0.68

2000

2.59

15.4

16.3

17.5

0.56

2500

3.1

18.2

19.3

20.7

0.56

2000

2.59

16.8

17.8

19.1

0.56

8

2500

3.1

20

21.2

22.7

0.56

ttt

Technical parameters of indoor dry-type transformer(35kV grade)

Technical parameters of SC(B)10 series 35kV dry-type transformer 1.0

Rated Capacity (kVA)

Voltage Combined

Vector- group

No-load Loss (w)

load Loss (w)
120ºC

No-load
current (%)

Short- circuit
impedance (%)

HV(KV)

Tapping Ranges

LV(KV)

50

35~38.5

±5%

±2×2.5%

0.4

Dyn11

Yyn0

450

1240

2.30

6.0

100

630

1830

2.00

160

790

2450

1.50

200

880

2900

1.50

250

990

3320

1.30

315

1170

3940

1.30

400

1370

4720

1.10

500

1620

5810

1.10

630

1860

6720

1.00

800

2160

7970

1.00

1000

2430

9080

0.75

1250

2830

11090

0.75

1600

3240

13450

0.75

2000

3820

15900

0.75

2500

4450

19040

0.75

Technical parameters of SC(B)10 series 35kV dry-type transformer 2.0

Rated power (kVA)

High voltage
(kV)

H.V.Tap
(kVA)

Low
Voltage
(kV)

Vector group

No-load
Current
(%)

Insulation
class

No-load
current (%)

Short circuit impedance

800

35
38.5

±5%

+2×2.5%

3.15

6

6.3

10

10.5

11

Yyn00
Dyn11

Yd11

2250

8210

0.95

6.0

1000

2670

9520

0.95

1250

3130

11270

0.85

1600

3690

13450

0.85

2000

4230

15900

0.75

2500

4860

19040

0.75

3150

6030

21400

0.70

4000

7020

25680

0.70

5000

8370

30480

0.60

6300

9900

35630

0.60

8000

Ynd11
Dyn11

Yd11

11300

40170

0.50

9.0

10000

12900

48470

0.50

12500

6

6.3

10

10.5

11

15700

56420

0.40

16000

19300

66380

0.40

20000

22900

74670

0.30

10.0

25000

27100

88210

0.30

Technical parameters of SC(B)11 series 35kV dry-type transformer

Rated Capacity (kVA) Voltage Combined Vector- group No-load Loss (w) load Loss (w)
120ºC
No-load
current (%)
Short- circuit
impedance (%)
HV(KV) Tapping Ranges LV(KV)
50 35~38.5 ±5%±2×2.5% 0.4 Dyn11Yyn0 405 1240 2.10 6
100 570 1830 1.80
160 710 2450 1.30
200 790 2900 1.30
250 890 3320 1.10
315 1050 3940 1.10
400 1230 4720 0.90
500 1460 5810 0.90
630 1670 6720 0.80
800 1940 7970 0.80
1000 2190 9080 0.60
1250 2550 11090 0.60
1600 2920 13450 0.60
2000 3440 15900 0.60
2500 4000 19040 0.60

Transformer Structure of Dry Type Power Transformer:

qq
qqqq

PERFORMANCE CHARACTERISTICS

1. No oil, no pollution, flame retardant, self-extinguishing and fire prevention.

2. Low loss, high efficiency and low noise. It can run long time under 125% rated load under the forced air-cooling condition and is equipped with intelligent temperature controller. The functions of fault alarm, over temperature  alarm, over temperature trip and black gate. It is connected with computer through RS485 serial interface and achieves centralized monitoring and control.

3. Small local discharge (under 30 PC) and high reliability, can ensure long-term safe operation, life up to 30 years.

4. Resistance to crack and temperature change, high mechanical strength, strong ability to resist sudden short-circuit.

5. Good moisture-proof property, it can run normally under 100% humidity and can be put into operation without drying treatment after shutdown.

6. There is no need for a separate transformer room, core maintenance or load-bearing beam  saving civil land and occupation No oil, so it will not produce toxic gas to pollute the environment.  No need of oil collecting pits or other ancillary buildings which reduces the cost of construction Easy installation, no debugging, almost no maintenance; No need to replace or check the oil, low operation and maintenance cost.